[ eljmkt: NEM Log | Gen / co2e / stn / Solcast | I/C's / today | Hour Ahead | Day Ahead: Region / I/C | Weather | News ]

[ To: N-Q-MNSP1 | NSW1-QLD1 | T-V-MNSP1 | V-S-MNSP1 | V-SA | VIC1-NSW1 ]

[NSW1-QLD1 Period: today | yesterday | last_sun | last_week ]

Interconnector Report (2017/10/11 to 2017/10/19)

Published: 2017/10/18 16:16:15

NSW1-QLD1


NSW1-QLD1 Summary

Quantity Export Import
Average Limit (MW) 293 822
Direction of Flow (%) 43.1 56.9
Energy Transfer (GWh) 20 45
Maximum Limit (MW) 573 1030
Maximum Flow (MW) 573 994
Interconnector Usage (%) 19.1 23.7

NSW1-QLD1 Export Constraints

Constraint ID Constraint Description Limited by (Hours) Bound (Hours)
F_Q++ARDM_R6 Out = one Armidale to Bulli Creek (8C; 8E; 8L or 8M) line; Qld Raise 6 sec Requirement [Version: 2013/08/21 #1] 29.92 11.58
N^Q_NIL_A Out= Nil; avoid Voltage Collapse on loss of Liddell to Muswellbrook (83) line [Version: 2013/08/21 #1] 35.00 6.92
N^^Q_NIL_B4 Out= Nil; avoid Voltage Collapse on loss of Tarong North [Version: 2013/08/21 #1] 14.92 0.50
N^^Q_NIL_B1 Out= Nil; avoid Voltage Collapse on loss of Kogan Creek [Version: 2013/08/21 #1] 67.67 0.42
#NSW1-QLD1_RAMP_E_F to be advised [Version: 2017/10/12 #1] 0.33 0.33
#R016288_005_RAMP_V to be advised [Version: 2017/10/12 #1] 0.25 0.25
Q>>BCRG_CLWU_BCCP to be advised [Version: 2017/05/29 #1] 0.25 0.25
F_Q++ARDM_R60 Out = one Armidale to Bulli Creek (8C; 8E; 8L or 8M) line; Qld Raise 60 sec Requirement [Version: 2013/08/21 #1] 1.75 0.08
F_Q++ARDM_R5 Out = one Armidale to Bulli Creek (8C; 8E; 8L or 8M) line; Qld Raise 5 min Requirement [Version: 2013/08/21 #1] 0.42 0.08
#R016303_003_RAMP_V to be advised [Version: 2017/10/12 #1] 0.17 0.08
#R016303_007_RAMP_V to be advised [Version: 2017/10/12 #1] 0.08 0.08
N^^Q_LS_VC_B1 Out= Lismore SVC; avoid Voltage Collapse on loss of Kogan Creek [Version: 2013/08/21 #1] 16.75 0.00
N^^Q_ARDM_B1 Out= one Armidale - Dumaresq (8C or 8E) line; avoid Voltage Collapse on loss of Kogan Creek [Version: 2013/08/21 #1] 5.83 0.00
N::Q_LDNC_KC Out= Liddell-Newcastle(81); NSW to Qld Transient Stability Limit for trip of Kogan Creek. [Version: 2013/08/21 #1] 4.33 0.00
#R016337_003_RAMP_F to be advised [Version: 2017/10/16 #1] 1.08 0.00
#R016344_003_RAMP_F to be advised [Version: 2017/10/18 #1] 1.08 0.00
#R016321_002_RAMP_F to be advised [Version: 2017/10/14 #1] 1.00 0.00
#R016328_002_RAMP_F to be advised [Version: 2017/10/15 #1] 0.83 0.00
#R016317_005_RAMP_F to be advised [Version: 2017/10/13 #1] 0.58 0.00
#R016324_001_RAMP_F to be advised [Version: 2017/10/15 #1] 0.58 0.00
#R016303_007_RAMP_F to be advised [Version: 2017/10/12 #1] 0.25 0.00
#R016303_005_RAMP_F to be advised [Version: 2017/10/12 #1] 0.08 0.00

NSW1-QLD1 Import Constraints

Constraint ID Constraint Description Limited by (Hours) Bound (Hours)
F_Q++ARDM_L6 Out = one Armidale to Bulli Creek (8C; 8E; 8L or 8M) line; Qld Lower 6 sec Requirement [Version: 2013/08/21 #1] 33.58 6.50
F_Q++ARDM_L5 Out = one Armidale to Bulli Creek (8C; 8E; 8L or 8M) line; Qld Lower 5 min Requirement [Version: 2013/08/21 #1] 4.83 4.83
#NSW1-QLD1_RAMP_I_F to be advised [Version: 2017/10/16 #1] 0.42 0.42
#NSW1-QLD1_RAMP_I_F to be advised [Version: 2017/10/15 #1] 0.42 0.42
#NSW1-QLD1_RAMP_I_F to be advised [Version: 2017/10/14 #1] 0.33 0.33
Q:N_NIL_AR_2L-G Out=Nil; limit Qld to NSW on QNI to avoid transient instability for a 2L-G fault at Armidale [Version: 2014/01/08 #1] 70.83 0.00
Q:N_NIL_BI_POT Out=Nil; limit Qld to NSW on QNI to avoid transient instability on trip of a Boyne Island potline (400 + j189 MVA) [Version: 2014/01/08 #1] 49.08 0.00
Q:N_BI_POT_WIV_N-2 to be advised [Version: 2017/08/02 #1] 10.58 0.00
Q:N_30+38_BI_POT Out= Liverpool-SydWest(30) + Regentville-SydWest(38) 330kV lines; limit Qld to NSW on QNI to avoid transient instability on trip of a Boyne Island potline (400 MW); 2008/2009 implementation [Version: 2013/08/21 #1] 7.58 0.00
Q:N_30+38_AR_2L-G Out= Liverpool-SydWest(30) + Regentville-SydWest(38) 330kV lines; limit Qld to NSW on QNI to avoid transient instability on 2L-G fault at Armidale [Version: 2014/01/08 #1] 1.67 0.00
#R016275_008_RAMP_F to be advised [Version: 2017/10/11 #1] 1.08 0.00
#R016303_009_RAMP_F to be advised [Version: 2017/10/12 #1] 0.58 0.00
#R016288_009_RAMP_F to be advised [Version: 2017/10/12 #1] 0.58 0.00
Q:N_DM_CB_AR_2L-G Outage = one Dumaresq 330kV CB (5312; 5322; 5332; 5342) O/S; limit Qld to NSW on QNI to avoid transient instability on 2L-G fault at Armidale [Version: 2014/01/08 #1] 0.42 0.00
Q:N_DM_CB_BI_POT Outage = one Dumaresq 330kV CB (5312; 5322; 5332; 5342) O/S; limit Qld to NSW on QNI to avoid transient instability on trip of a Boyne Island potline (400 + j189 MVA) [Version: 2014/01/08 #1] 0.42 0.00
#R016321_009_RAMP_F to be advised [Version: 2017/10/14 #1] 0.33 0.00
#R016317_009_RAMP_F to be advised [Version: 2017/10/13 #1] 0.25 0.00
#R016328_009_RAMP_V to be advised [Version: 2017/10/15 #1] 0.17 0.00


Region Summary

TOTALDEMAND AVAILABLEGENERATION RRP
max mean min max avg min max avg min
REGIONID
NSW1 8586 7299 5521 12695 11708 10625 300 83 47
QLD1 7369 5995 4766 10122 8687 7580 446 93 14
SA1 1762 1120 612 3141 2487 1853 350 71 -150
TAS1 1301 1078 844 2362 2171 1769 283 66 -0
VIC1 6145 4648 3545 8875 7687 6887 310 73 0

Region Summary by Region by Day
TOTALDEMAND AVAILABLEGENERATION RRP
max mean min max avg min max avg min
REGIONID SETTLEMENTDATE
NSW1 2017-10-11 8586 7533 5716 11383 11020 10625 300 96 49
2017-10-12 8337 7455 5774 12377 11643 11089 120 78 64
2017-10-13 8251 7441 5843 12614 11761 11084 133 88 63
2017-10-14 7673 6946 5832 12568 11968 11320 101 86 70
2017-10-15 7693 6664 5521 12573 11905 11305 93 74 65
2017-10-16 8352 7405 5681 12342 11904 11442 120 81 61
2017-10-17 8451 7563 5958 12695 11905 10989 140 79 59
2017-10-18 8239 7437 5942 11870 11474 10951 145 82 47
QLD1 2017-10-11 7369 6269 4991 8425 8161 7754 331 115 55
2017-10-12 7309 6209 4998 8334 8041 7765 446 141 73
2017-10-13 7054 6133 4916 8367 8199 7820 300 105 65
2017-10-14 6576 5693 4859 8511 8031 7580 251 85 65
2017-10-15 6772 5625 4778 10122 8982 7857 88 69 60
2017-10-16 7149 6069 4766 10092 9720 9194 122 71 14
2017-10-17 7222 6105 4791 9723 9377 8963 135 75 51
2017-10-18 6546 5776 4813 9626 9147 8616 138 75 42
SA1 2017-10-11 1356 1111 831 3141 2857 2675 252 57 0
2017-10-12 1373 1070 802 2800 2515 2110 90 55 9
2017-10-13 1401 1175 941 2506 2240 2101 181 95 50
2017-10-14 1336 1012 695 2800 2383 1971 102 73 -150
2017-10-15 1250 917 612 2824 2531 2142 82 65 55
2017-10-16 1541 1193 915 2661 2235 1853 136 83 54
2017-10-17 1762 1272 878 2857 2555 2092 350 70 -80
2017-10-18 1613 1259 987 2941 2628 2132 153 65 -94
TAS1 2017-10-11 1221 1065 883 2265 2175 2154 211 61 -0
2017-10-12 1227 1037 868 2321 2314 2202 80 46 9
2017-10-13 1301 1131 944 2362 2325 2255 119 70 35
2017-10-14 1274 1128 1012 2360 2278 2187 90 70 45
2017-10-15 1186 1079 991 2349 2278 2196 82 64 55
2017-10-16 1288 1092 918 2227 2010 1899 106 73 54
2017-10-17 1208 1043 878 2018 1961 1769 283 71 31
2017-10-18 1233 1037 844 2012 1939 1802 115 78 55
VIC1 2017-10-11 5422 4757 3575 8875 8586 8040 278 54 0
2017-10-12 5819 4752 3608 8568 8219 7833 89 56 10
2017-10-13 5792 4878 3781 8273 7734 7064 131 82 10
2017-10-14 4826 4247 3726 7198 7061 6923 98 85 69
2017-10-15 4742 4087 3636 7219 7074 6887 90 71 61
2017-10-16 5723 4832 3680 7778 7417 7146 123 82 58
2017-10-17 6145 4893 3545 8043 7658 7155 310 73 11
2017-10-18 6017 4786 3549 8006 7783 7513 152 79 11

Region Summary by Day by Region
TOTALDEMAND AVAILABLEGENERATION RRP
max mean min max avg min max avg min
SETTLEMENTDATE REGIONID
2017-10-11 NSW1 8586 7533 5716 11383 11020 10625 300 96 49
QLD1 7369 6269 4991 8425 8161 7754 331 115 55
SA1 1356 1111 831 3141 2857 2675 252 57 0
TAS1 1221 1065 883 2265 2175 2154 211 61 -0
VIC1 5422 4757 3575 8875 8586 8040 278 54 0
2017-10-12 NSW1 8337 7455 5774 12377 11643 11089 120 78 64
QLD1 7309 6209 4998 8334 8041 7765 446 141 73
SA1 1373 1070 802 2800 2515 2110 90 55 9
TAS1 1227 1037 868 2321 2314 2202 80 46 9
VIC1 5819 4752 3608 8568 8219 7833 89 56 10
2017-10-13 NSW1 8251 7441 5843 12614 11761 11084 133 88 63
QLD1 7054 6133 4916 8367 8199 7820 300 105 65
SA1 1401 1175 941 2506 2240 2101 181 95 50
TAS1 1301 1131 944 2362 2325 2255 119 70 35
VIC1 5792 4878 3781 8273 7734 7064 131 82 10
2017-10-14 NSW1 7673 6946 5832 12568 11968 11320 101 86 70
QLD1 6576 5693 4859 8511 8031 7580 251 85 65
SA1 1336 1012 695 2800 2383 1971 102 73 -150
TAS1 1274 1128 1012 2360 2278 2187 90 70 45
VIC1 4826 4247 3726 7198 7061 6923 98 85 69
2017-10-15 NSW1 7693 6664 5521 12573 11905 11305 93 74 65
QLD1 6772 5625 4778 10122 8982 7857 88 69 60
SA1 1250 917 612 2824 2531 2142 82 65 55
TAS1 1186 1079 991 2349 2278 2196 82 64 55
VIC1 4742 4087 3636 7219 7074 6887 90 71 61
2017-10-16 NSW1 8352 7405 5681 12342 11904 11442 120 81 61
QLD1 7149 6069 4766 10092 9720 9194 122 71 14
SA1 1541 1193 915 2661 2235 1853 136 83 54
TAS1 1288 1092 918 2227 2010 1899 106 73 54
VIC1 5723 4832 3680 7778 7417 7146 123 82 58
2017-10-17 NSW1 8451 7563 5958 12695 11905 10989 140 79 59
QLD1 7222 6105 4791 9723 9377 8963 135 75 51
SA1 1762 1272 878 2857 2555 2092 350 70 -80
TAS1 1208 1043 878 2018 1961 1769 283 71 31
VIC1 6145 4893 3545 8043 7658 7155 310 73 11
2017-10-18 NSW1 8239 7437 5942 11870 11474 10951 145 82 47
QLD1 6546 5776 4813 9626 9147 8616 138 75 42
SA1 1613 1259 987 2941 2628 2132 153 65 -94
TAS1 1233 1037 844 2012 1939 1802 115 78 55
VIC1 6017 4786 3549 8006 7783 7513 152 79 11


Out of Servivce Elements from Constraint Information

0 1
Out = South Morang 330 kV series capacitor bank only 2017-10-11 00:05:00 to 2017-10-17 13:55:00 [N^^V_SM_SCAP]
Out= LowerTumut-UpperTumut(64) 2017-10-13 05:05:00 to 2017-10-13 17:05:00 [N>>V-LTUT_E]
Out = one Armidale to Bulli Creek (8C 2017-10-12 06:05:00 to 2017-10-16 11:00:00 [F_NVS++ARDM_L5, F_NVS++ARDM_L6, F_NVS++ARDM_L...
Out = Comalco 220 kV CB 752 - swamp if CB in service in Dispatch 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [F_T++NIL_TL_L5_DS, F_T++NIL_TL_L60_DS, F_T++N...
Out= One of Lismore330-Lismore132 (9U8 2017-10-12 07:05:00 to 2017-10-12 13:30:00 [N>Q_LSLS_9U8]
Out = DarlingtonPt to Wagga(63) 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [N::V_DPWG_BWSW, N::V_DPWG_MSDD, N::V_DPWG_UTM...
Out = Hadspen to Palmerston No. 3 110 kV line 2017-10-11 07:05:00 to 2017-10-11 07:40:00 [T>T_HAPM_110_IMP_4E, T>T_HAPM_110_IMP_4T, T>T...
Out= Eraring-KempsCreek(5A1 or 5A2) 2017-10-11 00:05:00 to 2017-10-11 14:50:00 [N>N-ERKC_01]
Out = Rowville to Yallourn No. 7 or No. 8 220 kV line 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [V>V_ROYP78_1AR, V>V_ROYP78_1BR]
Out = Buronga to Balranald to Darlington Pt. (X5) 220 kV kV line 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [V>SML_BUDP_1]
Out = South Morang F2 500/330 kV txfmr 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [N^^V_SMTXF2_1, V>>V_SMTXF2_3R, V>>V_SMTXF2_4A...
Out = Buronga to Balranald to Darlington Pt. (X5) 220 kV line 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [N>>V_BUDP_1A, N>>V_BUDP_1B, V>>SML_BUDP_2, V>...
Out= South Morang F2 500/330 kV txfmr 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [N>>V_SMTXF2, N>>V_SMTXF2A, V>>N_SMTXF2, V>>N_...
Out = Lower Tumut to Upper Tumut 330 kV line 2017-10-13 05:05:00 to 2017-10-13 17:05:00 [N^^V_LTUT_1]
Out= DarlingtonPt-Wagga(63) 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [V>>V-DPWG_01, V>>V-DPWG_02]
Out = (Heywood to South East) or (Heywood transformers) or (Heywood to Mortlake) or (Heywood to Tarrone) or (Moorabool to Mortlake) or (Moorabool to Sydenham) or (Moorabool to Tarrone) 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [F_S++HYSE_L5, F_S++HYSE_L60, F_S++HYSE_L6_1, ...
Out = South Australia at credible risk of separation from NEM 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [S_V_ROCOF, V_S_ROCOF]
Out= Koolkhan to Lismore (967) and Lismore SVC 2017-10-17 06:05:00 to 2017-10-18 06:50:00 [N^N-967_LS_SVC]
Out= Liverpool-SydWest(30) + Regentville-SydWest(38) 330kV lines 2017-10-11 05:20:00 to 2017-10-11 15:00:00 [N:V_30+38_BYYS, Q:N_30+38_AR_2L-G, Q:N_30+38_...
Out= one Armidale - Dumaresq (8C or 8E) line 2017-10-12 06:05:00 to 2017-10-16 11:00:00 [N^Q_ARDM_B, N^^Q_ARDM_B1, N^^Q_ARDM_B2, N^^Q_...
Out= Lower Tumut-Murray(66) 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [N>>V-LTMS_2, V>>N-LTMS_1]
Out= Lower Tumut to Murray (66) line 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [N::V_LTMS]
Out = one Heywood to South East (HYTS-SESS) or other Heywood (HYTS) outage creating VIC-SA separation risk 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [F_ESTN++HYSE_L5, F_ESTN++HYSE_L6, F_ESTN++HYS...
Out= Liddell-Newcastle(81) 2017-10-13 11:05:00 to 2017-10-17 16:30:00 [N::Q_LDNC_KC, N::Q_LDNC_TNT, N:Q_LDNC_LDMU, N...
Out = Murray to Upper Tumut or Murray to Lower Tumut 330 kV line 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [N^^V_MSUTLT_2]
Out = Lower Tumut to Wagga 330kV line 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [V::N_LTWG_S1, V::N_LTWG_S2, V::N_LTWG_SD, V::...
Out = Hazelwood to South Morang 500kV line 2017-10-15 02:10:00 to 2017-10-15 06:45:00 [V::N_HWSM_S1, V::N_HWSM_SD, V::N_HWSM_V2]
Out= Tailem Bend 275kV Cap Bank (Note: with both Black Range series Caps I/S) 2017-10-11 00:05:00 to 2017-10-12 12:15:00 [V::S_TBCP1_MAXG, V::S_TBCP1_SETB, V^^S_TBCP1_...
Out =(Note: with both Black Range series capacitors I/S) 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [S:VS_700_OSC_AUTO]
Out= DarlingtonPt-Wagga(63) and Darlington Point to Buronga (X5) 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [V>>V-DPWG_X5_01X, V>>V-DPWG_X5_02X]
Out = one South Morang series capacitor 2017-10-11 00:05:00 to 2017-10-17 13:55:00 [V::N_SMSC_S1, V::N_SMSC_S2, V::N_SMSC_SD, V::...
Out= one Directlink cable 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [N_MBTE1_A, N_MBTE1_B]
Out= LowerTumut-Murray(66) 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [N>>N-LTMS_2, N>>N-LTMS_3, N>>N-LTMS_4, N>>V-L...
Out = Wagga-Yass 132 kV Parallel lines Opened and Yass-Marulan (5) 2017-10-11 06:05:00 to 2017-10-12 05:40:00 [N>>N-X_MNYS5_WGOP_08, N>>N-X_MNYS5_WGOP_13, N...
Out = Hazelwood to Cranbourne No.4 500kV line 2017-10-11 06:05:00 to 2017-10-11 14:55:00 [V::N_HWCB_Q1, V::N_HWCB_Q2, V::N_HWCB_S1, V::...
Out=Lower Tumut to Wagga (051) line 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [N::V_LTWG]
Out= Marulan-Yass(4 or 5) 2017-10-11 00:05:00 to 2017-10-12 05:40:00 [N:V_MNYS_BYYS]
Out = both or one Black Range series capacitors O/S 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [S:VS_BLKRG_700, S:V_BLKRG_550, V:SS_BLKRG_790...
Out = DarlingtonPt to Wagga(63) and Darlington Point to Buronga (X5) 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [N>>V-DPWG_X5_C, N>>V-DPWG_X5_D, V>>N-DPWG_X5_...
Out = both Black Range series capacitors O/S 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [V::S_BLKRG_MAXG_2, V::S_BLKRG_TBSE_2, V^^S_BL...
Out = Buronga to Balranald to Darlington Pt (X5) 220 kV line 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [N^^V_BUDP_1]
Out= Raleigh to Kempsey (9W2) and Boambee to Nambucca (9W7) avoid O/L Armidale to Coffs Harbour (96C) on trip of Armidale to Coffs Harbour (87) 2017-10-11 05:05:00 to 2017-10-14 12:20:00 [N>N-9W2_9W7_TE]
Out = One of Kemps Creek 500/330kV TX 2017-10-11 00:05:00 to 2017-10-17 17:50:00 [N>N-KC_TX_07]
Out= Lismore SVC 2017-10-17 06:05:00 to 2017-10-18 15:10:00 [N^Q_LS_VCB, N^^Q_LS_VC_B1, N^^Q_LS_VC_B2, N^^...
Out = South Morang F2 500/330kV txfmr 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [V::N_SMF2_S1, V::N_SMF2_S2, V::N_SMF2_SD1, V:...
Out = Any one 132 kV line between Ballina and Mullumbimby that opens the 132 kV path 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [N>N-BAMB_132_OPEN_A, N>N-BAMB_132_OPEN_B]
Out= Bayswater to Sydney West (32) 2017-10-14 05:20:00 to 2017-10-14 13:05:00 [N::Q_BWSW_KC]
Out = Lower Tumut to Wagga 330 kV line 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [N^^V_LTWG]
Out = Lower Tumut - Murray (66) line 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [N>>V_LTMS_1A]
Out = LowerTumut-UpperTumut(64) 2017-10-13 05:05:00 to 2017-10-13 17:05:00 [N>>V-LTUT_C, N>>V-LTUT_D, V>>N-LTUT_A, V>>N-L...
Out=Liverpool-SydWest(30) + Regentville-SydWest(38) 330kV lines 2017-10-11 05:20:00 to 2017-10-11 15:00:00 [N::V_30+38_BWSW, N::V_30+38_MSDD, N::V_30+38_...
Out= Tailem Bend 275kV Cap Bank (Note: with both Black Range series Caps O/S) 2017-10-11 00:05:00 to 2017-10-13 13:15:00 [V::S_TBCP1_SETB_2-DS, V^^S_TBCP1_MAXG_2-DS, V...
Out = Bayswater to Sydney West (32) 2017-10-14 05:20:00 to 2017-10-14 13:05:00 [N::Q_BWSW_TNT, N:Q_BWSW_LDMU, N:Q_BWSW_LDTW]
Out= Coffs Harbour to Raleigh (9W3) 2017-10-11 00:05:00 to 2017-10-18 15:10:00 [N>N-CHRL_TE_1]
Out = One Hadspen to Palmerston 110kV line 2017-10-11 07:05:00 to 2017-10-11 07:40:00 [T>T_HAPM_110_5A, T>T_HAPM_110_5B]
Out= Koolkhan to Lismore (967) 2017-10-11 00:05:00 to 2017-10-18 06:50:00 [N>N-KKLS_TE_2, N^N_KKLS_1]
Out = Lower Tumut to Wagga(051) 2017-10-11 06:05:00 to 2017-10-12 21:30:00 [V>>N-LTWG_RADIAL_1, V>>N-LTWG_RADIAL_2]
Out = One or both Black Range 275 kV series capacitors 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [V^S_HYCP_SC_OS]
Out= LowerTumut-UpperTumut(66) 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [V>>N-LTMS_1C]
Out = Lower Tumut to Murray 330 kV line 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [N^^V_LTMS]
Out = Hadspen to Palmerston No. 4 110 kV line 2017-10-11 07:05:00 to 2017-10-11 07:40:00 [T>T_HAPM_110_IMP_4F, T>T_HAPM_110_IMP_4R, T>T...
Out = One Heywood 500/275 kV txfmr (two remain in service) 2017-10-13 07:05:00 to 2017-10-14 15:40:00 [S:V_420_OSC_AUTO, S:V_580]
Out=Marulan-Yass(4 or 5) 2017-10-11 00:05:00 to 2017-10-12 05:40:00 [N::V_MNYS_BWSW, N::V_MNYS_MSDD, N::V_MNYS_UTM...
Out= 5A1 or 5A2 (Eraring to Kemps Creek) and One Kemps Creek 500/330kV Transformer 2017-10-11 00:05:00 to 2017-10-11 14:50:00 [N>>N-X_5A1_KCTX_2, N>>N-X_5A1_KCTX_4, N>>N-X_...
Out = Lower Tumut - Murray (66) line or Upper Tumut - Murray (65) line 2017-10-17 05:05:00 to 2017-10-18 15:10:00 [V::N_LT_UT_MS_S1, V::N_LT_UT_MS_S2, V::N_LT_U...
Out= Regentville - Sydney West (38) 2017-10-11 05:20:00 to 2017-10-11 15:00:00 [N::Q_RGSW_KC, N::Q_RGSW_TNT, N:Q_RGSW_LDMU, N...

[NSW1-QLD1 Period: today | yesterday | last_sun | last_week ]

[ To: N-Q-MNSP1 | NSW1-QLD1 | T-V-MNSP1 | V-S-MNSP1 | V-SA | VIC1-NSW1 ]

[ eljmkt: NEM Log | Gen / co2e / stn / Solcast | I/C's / today | Hour Ahead | Day Ahead: Region / I/C | Weather | News ]